Product Description
Applications:
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75°C maximum.
Construction:
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Standards:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum Conductors, Concentric-Lay-Stranded.
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75°C maximum.
Construction:
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Standards:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum Conductors, Concentric-Lay-Stranded.
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
| Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
| Size (AWG) | Strand- ing | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| 6201 ALLOY NEUTRAL-MESSENGER | |||||||||||
| Chihuahua | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 65 | 65 | 85 | 70 |
| Vizsla | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 68 | 68 | 85 | 70 |
| Harrier | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 99 | 99 | 115 | 90 |
| Whippet | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 103 | 103 | 115 | 90 |
| Schnauzer | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 157 | 157 | 150 | 120 |
| Heeler | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 250 | 250 | 205 | 160 |
| * Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++ Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. | |||||||||||
| Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
| Size (AWG) | Strand- ing | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAC NEUTRAL-MESSENGER | ||||||||||
| Pekingese | 6 | 1 | 45 | 6 | 7 | 563 | 61 | 61 | 85 | 70 |
| Collie | 6 | 7 | 45 | 6 | 7 | 563 | 64 | 64 | 85 | 70 |
| Dachshund | 4 | 1 | 45 | 4 | 7 | 881 | 92 | 92 | 115 | 90 |
| Spaniel | 4 | 7 | 45 | 4 | 7 | 881 | 96 | 96 | 115 | 90 |
| Doberman | 2 | 7 | 45 | 2 | 7 | 1350 | 147 | 147 | 150 | 120 |
| Malemute | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 234 | 234 | 205 | 160 |
| * Code Words For XLP Insulated Products Are Formed By Adding "/XLP" to the Conventional Code Words Above (e.g.-Chihuahua/XLP).+ Conductor Temperature of 90°C For XLP, 75°C For Poly; Ambient Temperature of 40°C; Emissivity 0.9; 2 ft./sec. Wind In Sun. | ||||||||||
| Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity | ||||||
| Size (AWG) | Strand- ing | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| ACSR NEUTRAL-MESSENGER | ||||||||||
| Setter | 6 | 1 | 45 | 6 | 6/1 | 1190 | 72 | 72 | 85 | 70 |
| Shepherd | 6 | 7 | 45 | 6 | 6/1 | 1190 | 75 | 75 | 85 | 70 |
| Eskimo | 4 | 1 | 45 | 4 | 6/1 | 1860 | 110 | 110 | 115 | 90 |
| Terrier | 4 | 7 | 45 | 4 | 6/1 | 1860 | 115 | 115 | 115 | 90 |
| Chow | 2 | 7 | 45 | 2 | 6/1 | 2850 | 176 | 176 | 150 | 120 |
| Bull | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 280 | 280 | 205 | 160 |
| * Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||