Product Description
Applications:
Used to supply 3 phase power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
Construction:
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Standards:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum conductors, Concentric-Lay-Stranded.
B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Used to supply 3 phase power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
Construction:
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Standards:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum conductors, Concentric-Lay-Stranded.
B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
| Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity | ||||||
| Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Stranding | Rated Strength (lbs). | XLP | POLY | XLP | POLY | |
| 6201 ALLOY NEUTRAL-MESSENGER | ||||||||||
| Bay | 6 | 1 | 45 | 6 | 7 | 1110 | 137 | 137 | 75 | 60 |
| French Coach | 6 | 7 | 45 | 6 | 7 | 1110 | 146 | 146 | 75 | 60 |
| German Coach | 4 | 1 | 45 | 4 | 7 | 1760 | 205 | 205 | 100 | 80 |
| Arabian | 4 | 7 | 45 | 4 | 7 | 1760 | 217 | 217 | 100 | 80 |
| Belgian | 2 | 7 | 45 | 2 | 7 | 2800 | 328 | 328 | 135 | 105 |
| Shetland | 1/0 | 9 | 60 | 1/0 | 7 | 4460 | 519 | 519 | 180 | 140 |
| Thoroughbred | 2/0 | 11 | 60 | 2/0 | 7 | 5390 | 639 | 639 | 205 | 160 |
| Trotter | 3/0 | 17 | 60 | 3/0 | 7 | 6790 | 789 | 789 | 235 | 185 |
| Walking | 4/0 | 18 | 60 | 4/0 | 7 | 8560 | 977 | 977 | 275 | 210 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Bay/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. | ||||||||||
| Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity | ||||||
| Size (AWG or kcmil) | Strand- ing | Insul. Thick. (mils) | Size (AWG or kcmil) | Strand- ing | Rated Strength (lbs). | XLP | POLY | XLP | POLY | |
| AAC NEUTRAL-MESSENGER | ||||||||||
| Clydesdale | 4 | 1 | 45 | 4 | 7 | 881 | 198 | 198 | 100 | 80 |
| Pinto | 4 | 7 | 45 | 4 | 7 | 881 | 211 | 211 | 100 | 80 |
| Mustang | 2 | 7 | 45 | 2 | 7 | 1350 | 318 | 318 | 135 | 105 |
| Criollo | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 503 | 503 | 180 | 140 |
| Percheron | 2/0 | 11 | 60 | 2/0 | 7 | 2510 | 619 | 619 | 205 | 160 |
| Hanovarian | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 764 | 764 | 235 | 185 |
| Oldenburg | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 945 | 945 | 275 | 210 |
| Lippizaner | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1519 | 1519 | 370 | 280 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Bay/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
| Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (Ibs.) | Allowable Ampacity | ||||||
| Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG or kcmil) | Stranding | Rated Strength (Ibs). | XLP | POLY | XLP | POLY | |
| ACSR NEUTRAL-MESSENGER | ||||||||||
| Morochuca | 6 | 1 | 45 | 6 | 6/1 | 1190 | 145 | 145 | 75 | 60 |
| Chola | 6 | 7 | 45 | 6 | 6/1 | 1190 | 153 | 153 | 75 | 60 |
| Morgan | 4 | 1 | 45 | 4 | 6/1 | 1860 | 217 | 217 | 100 | 80 |
| Hackney | 4 | 7 | 45 | 4 | 6/1 | 1860 | 229 | 229 | 100 | 80 |
| Palomino | 2 | 7 | 45 | 2 | 6/1 | 2850 | 347 | 347 | 135 | 105 |
| Costena | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 549 | 549 | 180 | 140 |
| Grullo | 2/0 | 11 | 60 | 2/0 | 6/1 | 5310 | 677 | 677 | 205 | 160 |
| Suffolk | 3/0 | 17 | 60 | 3/0 | 6/1 | 6620 | 837 | 837 | 235 | 185 |
| Appaloosa | 4/0 | 18 | 60 | 4/0 | 6/1 | 8350 | 1038 | 1038 | 275 | 210 |
| Gelding | 336.4 | 19 | 80 | 4/0 | 6/1 | 8350 | 1494 | 1494 | 370 | 280 |
| Bronco | 336.4 | 19 | 80 | 336.4 | 18/1 | 8680 | 1568 | 1568 | 370 | 280 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Bay/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||