Product Description
Applications:
Type UF-B cable is generally used as feeder to outside post lamps, pumps, and other loads or apparatus fed from
a distribution point in an existing building as specified in the National Electrical Code 1 . UF-B cable may be used
underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts.
Specifications:
Type UF-B cable meets or exceeds UL Standard 83, UL Standard 493, Federal Specification A-A-59544, and requirements of the National Electrical Code.
Construction:
Type UF-B cable is manufactured as a 2 or 3 conductor cable, with or without a ground wire. Copper conductors are annealed (soft) copper, solid or compressed stranded. Phase conductors are polyvinyl chloride (PVC) insulated, nylon jacketed, color coded for identification purposes. Jacketed with sunlight, moisture and fungus resistant gray PVC.
Type UF-B cable is generally used as feeder to outside post lamps, pumps, and other loads or apparatus fed from
a distribution point in an existing building as specified in the National Electrical Code 1 . UF-B cable may be used
underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts.
Specifications:
Type UF-B cable meets or exceeds UL Standard 83, UL Standard 493, Federal Specification A-A-59544, and requirements of the National Electrical Code.
Construction:
Type UF-B cable is manufactured as a 2 or 3 conductor cable, with or without a ground wire. Copper conductors are annealed (soft) copper, solid or compressed stranded. Phase conductors are polyvinyl chloride (PVC) insulated, nylon jacketed, color coded for identification purposes. Jacketed with sunlight, moisture and fungus resistant gray PVC.
| Conductor | Jacket Thickness (mils) | With Ground | Allowable Ampacity | |||||
| Size(AWG) | No. Strands | Insulation and Jacket Thickness (mils) | Ground Wire | Cable Dimension (mils) | Approx. Net Weight Per1000' (lbs.) | |||
| Size (AWG) | No. Strands | |||||||
| TWO CONDUCTOR | ||||||||
| 14 | 1 | 19 | 30 | 14 | 1 | 423 X 168 | 70 | 15 |
| 12 | 1 | 19 | 30 | 12 | 1 | 463 X 183 | 95 | 20 |
| 10 | 1 | 24 | 30 | 10 | 1 | 518 X 215 | 138 | 30 |
| 8 | 7 | 35 | 45 | 10 | 1 | 678 X 302 | 222 | 40 |
| 6 | 7 | 35 | 45 | 10 | 1 | 770 X 338 | 303 | 55 |
| THREE CONDUCTOR | ||||||||
| 14 | 1 | 19 | 30 | 14 | 1 | 581 X 168 | 96 | 15 |
| 12 | 1 | 19 | 30 | 12 | 1 | 626 X 183 | 129 | 20 |
| 10 | 1 | 24 | 30 | 10 | 1 | 727 X 215 | 191 | 30 |
| 8 | 7 | 35 | 45 | 10 | 1 | 1059 X 319 | 344 | 40 |
| 6 | 7 | 35 | 45 | 10 | 1 | 1223 X 361 | 478 | 55 |