Product Description
Conductor
Class B stranded tinned copper.
Insulation
FR-EPR flame retardant ethylene-propylene rubber per ICEA pub. no. S-68-516 part 3, Para. 3, 7 and UL requirements for EPCV insulated VW-1 conductors rated 90° C dry, 75° C wet.
Color Code
Phase conductors are black, printed "1", "2", and "3".
Cabling
Phase conductors are cabled together with class B stranded, tinned copper grounding conductor and suitable non-hygroscopic fillers. Cable assembly covered with a suitable tape.
Overall Jacket
Chlorinated polyethylene (CPE) meeting requirements of ICEA No. S-68-516, part 4 and sunlight resistant and oil resistant II requirements of UL 1277.
Features
Individual conductors shall be tested in accordance with UL requirements for type TC power and control cables having EPCW VW-1 insulated conductors and ICEA pub. S-68-516. Cables pass ribbon burner cable tray flame test requirements of UL and IEEE standard 383.
| Size (AWG or kcmil) | Stranding | Number of Conductors | Grounding Conductor (AWG or kcmil) | Avg. Overall Diameter (Inches) | Approximate Weight lbs./1000ft |
| 8 | 7 | 3 | 10 | .660 | 330 |
| 6 | 7 | 3 | 8 | .740 | 465 |
| 4 | 7 | 3 | 8 | .890 | 685 |
| 2 | 7 | 3 | 6 | 1.020 | 1015 |
| 1 | 19 | 3 | 6 | 1.150 | 1270 |
| 1/0 | 19 | 3 | 6 | 1.250 | 1500 |
| 2/0 | 19 | 3 | 6 | 1.340 | 1820 |
| 3/0 | 19 | 3 | 4 | 1.440 | 2250 |
| 4/0 | 19 | 3 | 4 | 1.590 | 2720 |
| 250 | 37 | 3 | 4 | 1.780 | 3310 |
| 350 | 37 | 3 | 3 | 2.010 | 4430 |
| 500 | 37 | 3 | 2 | 2.280 | 6150 |
| 750 | 61 | 3 | 1 | 2.810 | 8890 |
| 1000 | 61 | 3 | 1/0 | 3.160 | 11720 |