Product Description
XHHW Power Cable- 4 Conductor With Ground - Type TC - NEC® ARTICLE 340 - 90°C Wet & Dry- 600V
Construction
Conductor
Class B stranded uncoated copper conductor.
Insulation
XLP crosslinked polyethylene insulation, surface print phase identification (black and numbered).
Cabling
Four insulated conductors twisted with a class B stranded uncoated copper grounding conductor in two opposite valleys, suitable fillers, cable tape.
Jacket
PVC jacket overall, surface printed.
Application
As flame-retardant four conductor power cables rated 600 volts, 90° C in wet or dry locations. Specifically approved for installation in cable trays per Article 340 of the NEC. Type TC cables are approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Approvals
Listed by UL as type TC tray cable per Article 340 of the NEC.
Individual conductors UL listed as type XHHW-2.
Overall jacket UL listed as sunlight resistant.
Cables pass UL and IEEE- 383 ribbon burner flame tests.
Cables UL listed for direct burial.
Cables meet requirements of ICEA pub. no. S-66-524 and NEMA pub. no. WC7 for crosslinked polyethylene insulated wire and cable.
| Size (AWG or kcmil) | Stranding | Number of Conductors | Grounding Conductor (AWG or kcmil) | Avg. Overall Diameter (Inches) | Approximate Weight lbs./1000ft |
| 8 | 7 | 4 | 10 | .700 | 415 |
| 6 | 7 | 4 | 8 | .750 | 575 |
| 4 | 7 | 4 | 8 | .970 | 840 |
| 2 | 7 | 4 | 6 | 1.220 | 1200 |
| 1 | 19 | 4 | 6 | 1.360 | 1545 |
| 1/0 | 19 | 4 | 6 | 1.470 | 1835 |
| 2/0 | 19 | 4 | 6 | 1.470 | 2195 |
| 3/0 | 19 | 4 | 4 | 1.590 | 2800 |
| 4/0 | 19 | 4 | 4 | 1.800 | 3460 |
| 250 | 37 | 4 | 4 | 1.930 | 4040 |
| 350 | 37 | 4 | 3 | 2.200 | 5475 |
| 500 | 37 | 4 | 2 | 2.500 | 7635 |