Product Description
Applications:
Type RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the National Electrical Code. When used as Type USE-2, conductor is suitable for use as underground service entrance cable for direct burial at conductor temperatures not to exceed 90° C. When used as RHH, conductor temperatures shall not exceed 90°C in dry locations. When used as RHW-2 or USE-2, conductor temperatures shall not exceed 90°C in wet or dry locations. Voltage rating for RHH o RHW-2 or USE-2 conductors is 600 volts.
Specifications:
Type RHH or RHW-2 or USE-2 meets or exceeds UL Standard 44 (for RHH or RHW-2), UL Standard 854 (for
USE-2), ASTM B3 Soft or Annealed Copper Wire, ASTM B8 Concentric Lay Stranded Copper Conductors or ASTM 787 19
Wire Combination Unilay-Stranded Copper Conductors, Federal Specification A-A-59544, and requirements of the National Electrical Code. Sunlight Resistant. Colors available. Type RHH or RHW-2 or USE-2 meets and exceeds all construction requirements of ICEA S-95- 658 (NEMA WC 70) - Nonshielded 0 - 2 kV Cables, with testing frequencies based on UL requirements.
Construction:
Type RHH or RHW-2 or USE-2 copper conductors are annealed (soft) copper. Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linked polyethylene (XLP).
Type RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the National Electrical Code. When used as Type USE-2, conductor is suitable for use as underground service entrance cable for direct burial at conductor temperatures not to exceed 90° C. When used as RHH, conductor temperatures shall not exceed 90°C in dry locations. When used as RHW-2 or USE-2, conductor temperatures shall not exceed 90°C in wet or dry locations. Voltage rating for RHH o RHW-2 or USE-2 conductors is 600 volts.
Specifications:
Type RHH or RHW-2 or USE-2 meets or exceeds UL Standard 44 (for RHH or RHW-2), UL Standard 854 (for
USE-2), ASTM B3 Soft or Annealed Copper Wire, ASTM B8 Concentric Lay Stranded Copper Conductors or ASTM 787 19
Wire Combination Unilay-Stranded Copper Conductors, Federal Specification A-A-59544, and requirements of the National Electrical Code. Sunlight Resistant. Colors available. Type RHH or RHW-2 or USE-2 meets and exceeds all construction requirements of ICEA S-95- 658 (NEMA WC 70) - Nonshielded 0 - 2 kV Cables, with testing frequencies based on UL requirements.
Construction:
Type RHH or RHW-2 or USE-2 copper conductors are annealed (soft) copper. Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linked polyethylene (XLP).
| Conductor | Insulation Thickness (mils) | Nominal O.D. (mils) | Allowable Ampacity | Approx. Net Weight Per 1000' (lbs.) | ||||
| Size (AWG or kcmil) | No. Strands | 60°C | 75°C | 90°C | ||||
| 14 | 7 | 45 | 160 | 15 | 15 | 15 | 21 | |
| 12 | 7 | 45 | 177 | 20 | 20 | 20 | 30 | |
| 10 | 7 | 45 | 201 | 30 | 30 | 30 | 44 | |
| 8 | 7 | 60 | 262 | 40 | 50 | 55 | 72 | |
| 6 | 7 | 60 | 297 | 55 | 65 | 75 | 106 | |
| 4 | 7 | 60 | 344 | 70 | 85 | 95 | 156 | |
| 2 | 7 | 60 | 400 | 95 | 115 | 130 | 238 | |
| 1 | 19 | 80 | 484 | 110 | 130 | 150 | 309 | |
| 1/0 | 19 | 80 | 523 | 125 | 150 | 170 | 381 | |
| 2/0 | 19 | 80 | 567 | 145 | 175 | 195 | 472 | |
| 3/0 | 19 | 80 | 617 | 165 | 200 | 225 | 586 | |
| 4/0 | 19 | 80 | 673 | 195 | 230 | 260 | 729 | |
| 250 | 37 | 95 | 751 | 215 | 255 | 290 | 867 | |
| 300 | 37 | 95 | 804 | 240 | 285 | 320 | 1029 | |
| 350 | 37 | 95 | 854 | 260 | 310 | 350 | 1191 | |
| 400 | 37 | 95 | 899 | 280 | 335 | 380 | 1352 | |
| 500 | 37 | 95 | 983 | 320 | 380 | 430 | 1674 | |
| 600 | 61 | 110 | 1089 | 355 | 420 | 475 | 2012 | |
| 700 | 61 | 110 | 1158 | 385 | 460 | 520 | 2332 | |
| 750 | 61 | 110 | 1191 | 400 | 475 | 535 | 2492 | |
| 800 | 61 | 110 | 1223 | 410 | 490 | 555 | 2652 | |
| 900 | 61 | 110 | 1283 | 435 | 520 | 585 | 2970 | |
| 1000 | 61 | 110 | 1340 | 455 | 545 | 615 | 3288 | |