Product Description
EPR Hypalon® (5000V Unshielded) Type MV90- Power Cable- Wet and Dry Location
Construction
Conductor:
* Class B stranded annealed uncoated copper. Conductors shall be covered with a layer of extruded conducting thermosetting compound.
Insulation:
* EPR (ethylene propylene rubber) in accordance to paragraph 3.6 of ICEA.
Jacket:
* A Hypalon® jacket shall be applied directly over the insulation surface printed.
Application
* Where NEC jurisdiction applies; as 5,000- volt nonshielded power cable. Type MV- 90. for use at conductor temperatures not exceeding 90°C in wet or dry locations. Cables meet requirements of Article 310.6 of the National Electrical Code.
* For other applications, as nonshielded power cables for use at 5000 volts 100% insulation level (grounded neutral) and 133% insulation level (ungrounded neutral) under the following conditions:
1. Single conductors mounted on insulators in free air in indoor or outdoor locations. Circuit voltages are 2400 volts, 4160 volts and 4800 volts.
2. Random lay singles in metal conduit and nonmetallic conduit in dry locations at circuit voltage of 2400 volts. 4160 volts and 4800 volts, and in damp or wet locations at circuit voltages of 2400 volts and 4160 volts.
3. Triplexed singles in metal conduit and nonmetallic conduit in damp or wet location at circuit voltages of 4800 volts.
4. Single conductors or triplexed singles in cable tray, spaced block supports or in messenger supported rings in dry, damp or wet locations at circuit voltages of 2400 volts and 4160 volts.
5. Triplexed singles in cable tray, spaced block supports or in messenger supported rings in damp or wet locations at circuit voltage of 4800 volts.
6. Single conductors or triplexed singles, aerially, field-spun to grounded messenger in dry, damp or wet locations at circuit voltages of 2400 volts 4160 volts and 4800 volts.
Approvals
* Listed by UL as 5,000 volt nonshielded cable, Type MV-90, per UL standard 1072.
* Conforms to ICEA pub. no. S-68-516 and NEMA pub. no. WC8 for ethylene-propylene-rubber-insulated wire and cable.
* Sizes 1/0 AWG and larger pass UL and IEEE standard 383 ribbon burner flame test and are UL listed for CT use.
| Size (AWG) | Nominal Strands | Nominal Overall Diameter (Inches) | Approximate New Weight LBS/M | Current-Duct Amps |
| 6 | 7 | .650 | 260 | 85 |
| 4 | 7 | .700 | 330 | 110 |
| 2 | 7 | .760 | 435 | 145 |
| 1 | 19 | .800 | 506 | 170 |
| 1/0 | 19 | .840 | 590 | 195 |
| 2/0 | 19 | .880 | 700 | 220 |
| 3/0 | 19 | .960 | 860 | 250 |
| 4/0 | 19 | 1.020 | 1020 | 290 |
| 250MCM | 37 | 1.140 | 1210 | 320 |
| 350MCM | 37 | 1.240 | 1525 | 385 |
| 500MCM | 37 | 1.370 | 2130 | 470 |
| 750MCM | 61 | 1.620 | 3090 | 585 |
| 1000MCM | 61 | 1.760 | 3960 | 670 |
.